Conair Hopper Temperature Controller UGD031 Manuel d'utilisateur Page 66

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 97
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 65
Before Beginning
You can avoid most problems by following the recommended installation and
maintenance procedures outlined in this User Guide. If you do have a problem,
this section will help you determine what caused it and how to fix it.
Before you start disassembling the HTC process air heater be sure to:
Diagnose causes from the control panel.
1 Press the Acknowledge Alarm button to silence the alarm.
2 Address the alarm message and fix the problem.
3 Move the heater switch from Enable to Standby.
4 Cycle the heater switch from Standby to Enable to restart normal con-
trol. If the alarm reappears the problem was not fixed.
If the alarm is a passive alarm
you will see P in the screen title display.
If the alarm is a shut down alarm you will see A in the screen title
display.
Diagnose causes from the control panel.
You can locate any problem from the front of the heater.
Heaters
Startup /
Shutdown
For Startup:
1. With heaters in
Standby, turn on
blower or dryer.
2. Enable heaters.
For Shutdown:
1. Switch heaters to
Standby. 
2. Wait 60 seconds
before turning off
blower or dryer.
Enable
Standby
Acknowledge
Alarm Button
Scroll
Button
6-2 l
T
roubleshooting
Vue de la page 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 96 97

Commentaires sur ces manuels

Pas de commentaire