EarthSmart
TM
ECM Series, 0.50 to 0.75 ton models
Corporate Office: 724-584-5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and Service: 814.437.6861
USER GUIDE
UGH031-0209
www.conairgroup.com
Vue de la page 0
1 2 3 4 5 6 ... 71 72

Résumé du contenu

Page 1 - EarthSmart

EarthSmartTMECM Series, 0.50 to 0.75 ton modelsCorporate Office: 724-584-5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and

Page 2

ATTENTION:Read this so no one gets hurtWe design equipment with the user’s safety in mind. You can avoid the potentialhazards identified on this machi

Page 3 - Table of Contents

1IntroductionIntroduction l 1-5CAUTION: Hot SurfacesAlways protect yourself from hot surfaces when working on thechiller, especially when working on

Page 4 - A Appendix

1-6 l Introduction

Page 5 - Table of Contents l iii

Description l 2-1DescriptionWhat is the EarthSmart ECM Series Chiller?. . 2-2Typical applications . . . . . . . . . . . . . . . . . . 2-2Limitations

Page 6

What is the EarthSmart ECM SeriesChiller?The Conair EarthSmart ECM Series Chillers provide self-contained sources ofchilled water and are available wi

Page 7 - Introduction

Description l 2-32DescriptionLimitationsConair EarthSmart ECM Series Chillers are chosen based on the cooling load,ambient temperature and cooling t

Page 8 - How the Guide is Organized

2-4 l DescriptionHow it Works: Process CirculationHot fluid from the process enters the chillerthrough the “From Process” inlet into thechiller’s res

Page 9 - Your Responsibility as a User

2DescriptionDescription l 2-5How it Works: Refrigerant CirculationThe evaporator extracts heat from the process fluid,causing the refrigerant to vap

Page 10 - Read this so no one gets hurt

How it Works: Component ListingWater system• Motor/Pump assembly - The motor/pump assembly circulates chilled coolant through the process loop. The pu

Page 11

• Evaporator - The evaporator is a brazed plate heat exchanger where the liquid refrigerant is allowed to evaporate (boil off) to absorb the heat (BTU

Page 12 - 1-6 l Introduction

Please record your equipment’smodel and serial number(s) andthe date you received it in thespaces provided.It’s a good idea to record the model and se

Page 13 - Description

2-8 l DescriptionSpecifications: EarthSmartTMECMSeries ChillersABCTPHS039-1208MODEL ECM-0.5 ECM-0.75Performance characteristicsCapacity* tons 0.41

Page 14 - Typical Applications

Description l 2-92DescriptionPump Curve: EarthSmartTMECMSeries Chillers2550 75 100 125 150 175 200 225 250252030405060708090100110120130140100.000.0

Page 15 - Limitations

2-10 l Description

Page 16 - 2-4 l Description

Installation l 3-1InstallationUnpacking the boxes . . . . . . . . . . . . . . . . . 3-2Warnings and cautions . . . . . . . . . . . . . . . . 3-3Prep

Page 17 - Drain/Fill

3-2 l InstallationUnpacking the BoxesThe EarthSmart ECM Series Chiller comes fully assembled in a single crate.Units are shipped with the casters att

Page 18 - Refrigeration system

Installation l 3-33InstallationWarnings and CautionsWARNING: Improper installation, operation, orservicing may result in equipment damage or persona

Page 19 - Schematic

Preparing for InstallationPlan the location for the chiller and prepare the area properly.Position the chiller as close to the process machine as poss

Page 20 - Series Chillers

Installation l 3-53InstallationMaking Process PlumbingConnectionsAll process piping materials (such as hoses, rigid piping, valves or filters) usedw

Page 21 - Pump Curve: EarthSmart

3-6 l InstallationFilling the ChillerThe chiller is shipped without coolant. The chiller is manually filled during instal-lation using water as its c

Page 22 - 2-10 l Description

Installation l 3-73InstallationDrain ConnectionTo drain the chiller for storage or transport:1 Rotate the chiller’s drain valve counterclockwise. If

Page 23 - Installation

Table of Contents1-1 IntroductionPurpose of the user guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2How the guide is organiz

Page 24 - Unpacking the Boxes

3-8 l InstallationChecking the Refrigerant ChargeWARNING: Refrigerant hazardOnly certified refrigerant technicians should examine and correct problem

Page 25 - Warnings and Cautions

Connecting the Main PowerThe Conair EarthSmart ECM Chiller uses standard 115 Volt, 60 Hz or 220 Volt,60Hz single-phase power, depending on model.To co

Page 27 - Connections

SECTION44OperationOperationEarthSmart ECM Series Chiller:Control descriptions . . . . . . . . . . . . . . . 4-2Starting the chiller . . . . . . . . .

Page 28 - Filling the Chiller

12 %SDEarthSmart ECM Chiller: Control DescriptionsHot-GasBypass StatusIndicates the statusof the Hot-GasBypass valve.Actual ChillerTemperatureShows th

Page 29 - Drain Connection

4OperationOperation l 4-3Starting the ChillerTo start the chiller:1 Toggle the power switch to the On or “I” position. The control display willillu

Page 30 - WARNING: Refrigerant hazard

4-4 l OperationStopping the ChillerTo stop the chiller:1 Toggle the power switch to the Off or “O” position. Off Position12 %SDIMPORTANT: Do NOT rap

Page 31 - Connecting the Main Power

4OperationOperation l 4-5Changing Temperature Unit To stop the chiller:1 Press the green “Return” button once to access the Temperature Unit

Page 32 - 3-10 l Installation

4-6 l OperationChiller Operation SequenceThe EarthSmart ECM Series Chiller has a unique user interface that controls theprocess temperature and prev

Page 33 - Operation

Operation l 4-74OperationChiller Operation Sequence (continued)5 The condenser fan can energize anytime the toggle switch is in the “On” or “I” posi

Page 34

Stopping the chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4Changing temperature units . . . . . . . . . . . . .

Page 35 - Starting the Chiller

4-8 l OperationResetting the High Pressure Switchof the CompressorThe high refrigeration safety pressure switch shuts off the compressor immedia

Page 36 - Stopping the Chiller

MaintenancePreventative maintenance schedule . . . . . . . 5-2Checking electrical connections. . . . . . . . . . 5-4Cleaning the brazed plate adapter

Page 37 - Changing Temperature Unit

5-2 l MaintenancePreventative Maintenance ScheduleDaily, or as often as needed❒Checking process fluid level in the pump tankCheck the process fluid l

Page 38 - Chiller Operation Sequence

Maintenance l 5-3Preventative Maintenance Schedule(continued)Monthly❒Inspecting cooling water treatment systemIf your chiller uses a cooling water t

Page 39 - Operation l 4-7

5-4 l MaintenanceChecking Electrical Connections WARNING: Electrical HazardBefore performing any work on this item, disconnect and lock out electrica

Page 40 - 4-8 l Operation

Cleaning the Brazed Plate Evaporator Minerals and other contaminants produce deposits, scales, slime or algae on the heattransfer surfaces exposed to

Page 41 - Maintenance

5-6 l MaintenanceCleaning the Brazed Plate Evaporator (continued)5 Remove RTD from bottom of evaporator.6 Connect 3/8-inch tubing to the 3/8-inch con

Page 42 - (continued)

5MaintenanceCleaning the Air-Cooled CondenserWARNING: Electrical HazardBefore performing any work on this item, disconnect and lock out electricalpowe

Page 43 - Maintenance l 5-3

Cleaning the Air-Cooled Condenser(continued)7 Check the air filter. If the filter is blinded or torn, replace the filter.8 Replace the chiller’s side

Page 44 - 5-4 l Maintenance

Maintenance l 5-9Checking Reservoir Level WARNING: Electrical HazardBefore performing any work on the chiller, disconnect and lock out electricalpow

Page 45 - Water level gauge

B AppendixSafety adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1C AppendixWater quality control . . . . . .

Page 46 - NOTE: These connections

Cleaning the Pump StrainerEarthSmart Chillers use a rotary pump to flow process coolant through their internalpiping and to the process. A strainer on

Page 47

Cleaning the Pump Strainer (continued)6 Remove the strainer from its housing.7 Inspect the strainer for holes or blinding, clean or replace as necessa

Page 48 - CAUTION: Wear eye protection

5-12 l MaintenanceChecking the Refrigerant Charge andQualityWARNING: Refrigerant HazardOnly certified refrigerant technicians should examine and corr

Page 49 - Checking Reservoir Level

TroubleshootingBefore beginning. . . . . . . . . . . . . . . . . . . . 6-2A few words of caution . . . . . . . . . . . . . . 6-3DIAGNOSTICSHow to id

Page 50 - Cleaning the Pump Strainer

Before BeginningYou can avoid most problems by following the recommended installation andmaintenance procedures outlined in this User Guide. If you d

Page 51 - Maintenance l 5-11

6TroubleshootingA Few Words of CautionImproper corrective actions can lead to hazardous conditions and shouldnever be attempted to sustain production.

Page 52 - WARNING: Refrigerant Hazard

6-4 l TroubleshootingAlarmsIf the red alarm LED is illuminated, an alarm is activated. The chiller has automat-ically pumped down because it has det

Page 53 - Troubleshooting

Troubleshooting l 6-56TroubleshootingTroubleshootingProblemThe chiller will not start.(Control not illuminated)Pump will not start.Possible causeTri

Page 54 - Before Beginning

Troubleshooting (continued)ProblemCompressor will not start.Possible causeHigh pressure switch has been tripped. Circuit breaker has been tripped.Loos

Page 55 - A Few Words of Caution

Troubleshooting (continued)ProblemChiller shuts down due to aHigh Pressure switch alarm.Chiller shuts down due to aLow Pressure switch.Possible causeL

Page 56 - Solution

iv l Table of Contents

Page 57

Checking or Replacing theTemperature SensorThe EarthSmart ECM Series Chiller uses a RTD sensor to monitor the temperatureof the process coolant.To che

Page 58 - Troubleshooting (continued)

Troubleshooting l 6-9Checking or Resetting the CircuitBreakersThe EarthSmart ECM Series Chiller uses electrical circuit breaker to protect thechille

Page 59

A-1 l AppendixWe’re Here to HelpConair has made the largest investment in customer support in the plastics indus-try. Our service experts are availab

Page 60 - Temperature Sensor

Appendix l A-2Equipment GuaranteeConair guarantees the machinery and equipment on this order, for a period asdefined in the quotation from date of s

Page 61 - Breakers

B-1 l AppendixSafety AdjustmentsTo ensure safe and efficient operation at lower setpoints, adjustments of thelow pressure switch from factory setting

Page 62 - PARTS & SERVICE

Appendix l C-1Water Quality ControlInsufficient or improper water treatment can damage the EarthSmart ECM Chiller.A certified water treatment specia

Page 63 - Warranty Limitations

D-1 l AppendixChiller Capacity and Derate ChartIf operation of the chiller is less than 45°F {7.2°C}, a glycol and water mixtureis required. See Oper

Page 64 - Safety Adjustments

Appendix l E-1Pressure-Temperature Chart forR-134A RefrigerantRefrigerant Pressure (PSIG)51015202530354045505560657075808590951001051101151201251301

Page 65 - Water Quality Control

F-1 l AppendixRTD Resistance ChartYou can use the following chart to determine if you need to replace your RTD.

Page 66 - See Installation sec

Appendix l G-1Overhead Plumbing DetailsOverhead piping installations above process connections require installing a checkvalve in the “To Process” l

Page 67 - R-134A Refrigerant

IntroductionPurpose of the user guide. . . . . . . . . . . . . . 1-2How the guide is organized . . . . . . . . . . . . . 1-2Your responsibilities as a

Page 68 - RTD Resistance Chart

H-1 l AppendixElectrical Schematic 9.009.008.008.004.044.041TC1TC1ENC1ENC1CAB1CAB1SW1SW2CB2CB1CB1CB1TB1TB1GB1GB12222346778910102ENC2ENC1TC1TC1SW1SW7

Page 69 - Overhead Plumbing Details

Appendix l I-1Control Setup1/32 DIN Watlow SD controller Setup SheetEnter the following parametersMenu Parameter Description SettingSet Up Page Sen

Page 70 - Electrical Schematic

Plumbing SchematicFROM PROCESS 12"TO PROCESS 12"LEVELWATE RTA NK1PSLFS1EVAPORATOR (1/4" schraeder valve)PI1RANGE= 40 TO 65 °FTAH H1STE1

Page 71 - Control Setup

✐Purpose of the User GuideThis User Guide describes the EarthSmart ECM Series Chiller andexplains step-by-step how to install, operate, maintain and r

Page 72 - Plumbing Schematic

Introduction l 1-3Your Responsibility as a UserYou must be familiar with all safety procedures concerning installation, opera-tion and maintenance o